Metalaire

Jeremias is one of the world’s leading manufacturers of flue and chimney systems for the exhaust of gases and ventilation, covering all kinds of domestic, commercial and industrial applications. Jeremias Group product range includes over 50 different CE of UL certified systems covering commercial and domestic applications complimenting freestanding industrial steel chimneys up to 10 feet in diameter. Jeremias offers its clients a wide range of high-quality products, technical support for projects, and stack sizing software.

Energy International is the Authorized Distributor for Jeremias in the Middle East. For more information on Jeremias products contact your Energy International representative.

Jeremias Representative

In Riyadh, KSA

Mazen Sheet
T:+966-11-476-2755
M:+966-56-424-8924
msheet@energyintl.com

In Jeddah, KSA

Fadi Fakih
T:+966-12-662-9368
M:+966-53-428-6827
fadi.fakih@energyintl.com

In Dammam, KSA & Bahrain

Marwan Mroueh
T:+966-13-834-7837‬
M:+966-53-030-8349
marwan.mroueh@energyintl.com

In The UAE & Oman

Khalil Bilan
T:+971-6-534-3477
M:+971-50-818-5351
k.bilan@energyintl.com

In Lebanon

Bechara Saab
T:+961-5-450-610
M:+961-3-305-816
bsaab@energyintl.com

In Jordan

Fadi Rashid
T:+962-6-556-1718
M:+962-79-7565677
fadi.rashid@energyintl.com

In Qatar

Ammar Assi
T:+974-44-58-1126
M:+974-55-50-6143
aassi@energyintl.com

Single wall stainless steel exhaust systems for relining and connection pipes

Main advantages of Jeremias single wall exhaust systems:
– UL listed
– Easy installation due to perfect fitting plug-in system
– No welding on site needed
– Corrosion-free stainless steel
– Condensate- and gas-proof materials

SWKL

SWKL

Pressure-tight insulated exhaust system without any gasket, made of stainless steel
Description: Single Wall Conical all-in-one chimney and exhaust system
Material: 444 stainless steel. Optional 304, 316L, or 430 stainless steels
Wall thickness: 0.035″ thick
Diameter: 5 – 36 inch
Connection: Conical, gasket free
Locking Band: Attached to each part

SWKL vt

SWKL vt

Pressure-tight insulated exhaust system without any gasket, made of stainless steel
Description: Single Wall Conical -Lighter gauge all-in-one chimney and exhaust system
Material: 444 stainless steel
Wall thickness: 0.020″ thick
Diameter: 3 – 18 inch
Connection: Conical, gasket free
Locking band: Attached to each part

SWFL

SWFL

Single wall flanged joining pipe & fittings
Description: Single Wall all-in-one exhaust system
Material: 444 or 316L stainless steel. All supports and accessories are 304 stainless steel
Wall thickness: 0.035″ thick
Diameter: 6” – 36” I.D.
Connection: Inner connection is a 1.25” conical overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal.
Locking Band: Attached to each part

SWGV

SWGV

Pressure-tight insulated exhaust system made of stainless steel
Description: Single Wall Special Gas Vent
Inner Liner Material: ASTM 316L highgrade stainless steel
Wall thickness: 0.020″ (diameters 3 – 12″), 0.035″ (diameter 13 -36″)
Diameter: 3″ – 36″ I.D.
Connection: Ø3″ – Ø12″ – Industry leading 2.28” overlapping joint with silicone 3-ribbed gasket
Ø13″ – Ø36″ – Connection is a 1.25” conical overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal.

SWGD

SWGD

Single wall grease duct for connecting cooking appliances and grease hoods
Description: Single Wall Grease Duct
Material: ASTM 304 stainless steel
Wall thickness: per UL-1978 Listing
Diameter: 3 – 16 inch, 18 – 36 inch
Connection: Conical
Locking Band: Attached to each part

Double Wall Exhaust Systems. Insulated exhaust system made of stainless steel

Main advantages of Jeremias double wall exhaust systems
– UL listed
– Easy installation due to perfect fitting plug-in system
– No welding on site needed
– High quality insulation
– No thermal bridges between inner and outer tube
– Corrosion-free stainless steel
– Condensate- and gas-proof materials

DWKL

DWKL

Pressure-tight insulated exhaust system without any gasket, made of stainless steel
Description: Double Wall Conical all-in-one chimney and exhaust system
Inner Material: 444 stainless steel. Optional 304, 316L, or 430 stainless steels
Outer Jacket Material: 304 polished stainless steel. Optional matt, powder coated, brushed, or copper
Wall thickness: Inner Liner 0.035″. Outer Jacket 0.025″ (dia. 5″ – 24″). Outer Jacket 0.035″ (dia. 26″ – 36″)
Inner diameter: 5-36 in
Insulation: Ceramic Fiber, 1.5″ thick compressed to 1.25″ space
Connection: Conical, gasket free
Locking band: Attached to each part

DWKL-Lt

DWKL-Lt

Pressure-tight insulated exhaust system without any gasket, made of stainless steel
Description: Double Wall -Lighter gauge inner Conical all-in-one chimney and exhaust system
Inner Liner Material: 444 stainless steel. Optional 304, 316L, or 430 stainless steels
Outer Jacket Material: 304 polished stainless steel. Optional matt, powder coated, brushed, or copper:
Wall thickness: Inner Liner 0.020″ thick. Outer Jacket 0.025″ thick
Inner diameter: 3 – 18 inch
Insulation: Ceramic Fiber, 1.5″ thick compressed to 1.25″ space
Connection: Conical, gasket free
Locking band: Attached to each part

DWKL-Vt

DWKL-Vt

Pressure-tight insulated exhaust system without any gasket, made of stainless steel
Description: Double Wall -Vent Conical all-in-one chimney and exhaust system
Inner Liner Material: 444 stainless steel
Outer Jacket Material: 304 polished stainless steel. Optional matt, powder coated, brushed, or copper
Wall thickness: Inner Liner 0.020″ thick. Outer Jacket 0.025″ thick
Inner diameter: 3 – 18 inch
Insulation: 1.25″ thick cut fiber insulation
Connection: Conical, gasket free
Locking band: Attached to each part

DWKL-Rx

DWKL-Rx

Pressure-tight insulated exhaust system without any gasket, made of stainless steel
Description: Double Wall Conical all-in-one chimney and exhaust system
Inner Liner Material: 444 stainless steel
Outer Jacket Material: 304 polished stainless steel. Optional matt, powder coated, brushed, or copper
Wall thickness: Inner Liner 0.035″ , Outer Jacket 0.025″ (diameters 5 – 24 inch), Outer Jacket 0.035″ (diameters 26 – 36 inch)
Inner diameter: 5 – 36 inch
Insulation:
Rx, 1.25” thick cut fiber insulation
Rx+2, 2.25” thick cut fiber insulation
Rx+3, 3.25” thick cut fiber insulation
Rx+4, 4.25” thick cut fiber insulation
Rx+5, 5.25” thick cut fiber insulation
Rx+6, 6.25” thick cut fiber insulation
Connection: Conical, gasket free
Locking band: Attached to each part

DWFL

All-in-one exhaust, chimney or vent
Description: DWFL – Double Wall Flanged Joint
Inner Material: Inner liner made of high-grade 444 stainless steel
Outer Jacket Material: Outer jacket made of 304 stainless steel
Wall thickness: Inner, 5” thru 36” = 0.035” thick. Outer, 5” thru 24” = 0.025” thick, 26” thru 36” = 0.035” thick
Inner diameter: 6” – 36” I.D.
Insulation: 1.25” Air
Connection: Inner connection is a 1.25” conical overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal. Blanket insulation and outer band completes the joint assembly.
Locking band: Attached to each part

DWFL +1, +2, +3 and +4

DWFL

All-in-one exhaust, chimney or vent
Description: DWFL – Double Wall Flanged Joint
Inner Material: Inner liner made of high-grade 444 stainless steel
Outer Jacket Material: Outer jacket made of 304 stainless steel
Wall thickness: Inner, 5” thru 36” = 0.035” thick. Outer: 5” thru 24” = 0.025” thick: 26” thru 36” = 0.035” thick
Inner diameter: 6” – 36” I.D.
Insulation: Ceramic fiber insulation at: 1.25”, 2.25”, 3.25”, or 4.25” thick fiber
Connection: Inner connection is a 1.25” conical overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal. Blanket insulation and outer band completes the joint assembly.
Locking band: Attached to each part

DWFL-ZC Grease Duct

DWFLG

Zero clearance & fire rated grease duct
Description: DWFL-ZC UL-2221 Zero Clearance & Fire Rated Grease Duct
Inner Material: Inner liner made of high-grade ASTM 316L stainless steel.
Outer Jacket Material: Outer jacket made of ASTM 304 stainless steel
Wall thickness: Inner, 6” thru 36” = 0.035” thick, Outer: 6” thru 24” = 0.025” thick, 26” thru 36” = 0.035” thick
Inner diameter: 6” – 36” I.D.
Insulation: 3.25” thick compressed ceramic fiber insulation
Connection: Inner connection is a 1.25” overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal. Blanket insulation and outer band completes the joint assembly.
Locking band: Attached to each part

DWFL-ZC Gas Vent

DWFLG

Zero clearance & fire rated grease duct
Description: DWFL-ZC UL-2221 Zero Clearance & Fire Rated Grease Duct
Inner Material: Inner liner made of high-grade ASTM 316L stainless steel.
Outer Jacket Material: Outer jacket made of ASTM 304 stainless steel
Wall thickness: Inner, 6” thru 36” = 0.035” thick, Outer: 6” thru 24” = 0.025” thick, 26” thru 36” = 0.035” thick
Inner diameter: 6” – 36” I.D.
Insulation: 3.25” thick compressed ceramic fiber insulation
Connection: Inner connection is a 1.25” overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal. Blanket insulation and outer band completes the joint assembly.
Locking band: Attached to each part

DWGV

DWGV

Pressure-tight air-insulated exhaust system made of stainless steel
Description: Double Wall Special Gas Vent
Inner Liner Material: 444 or ASTM 316L stainless steel
Outer Jacket Material: ASTM 304 stainless steel – BA Finish
Wall thickness:
Inner Liner 0.020″ (diameter 3” – 12″ I.D.)
Inner Liner 0.035″ (diameter 13” – 36″ I.D.)
Outer Jacket 0.020″ (diameters 3” – 12” I.D.)
Outer Jacket 0.025″ (diameters 13” – 24” I.D.)
Outer Jacket 0.035″ (diameters 26” – 36” I.D.)
Inner diameter: 3 – 36”
Insulation: Ø3 – Ø12” – 1” insulating air space. Ø13 – Ø36” – 1.25” insulating air space
Connection: Ø3 – Ø12” – Industry leading 2.28” overlapping joint with silicone 3-ribbed gasket Ø13 – Ø36” – Inner connection is a 1.25” conical overlapping joint with added ½” rolled flange and vee band connection. Supplied sealant is used in the vee band to make seal.
Locking band: Attached to each part

ECCO Type B Gas Vent

ECCO

Exhaust for category one appliances only
Description: Double Wall Type B Gas Vent
Inner Liner Material: Inner liner made of Aluminum Alloy
Outer Jacket Material: Outer jacket made of Galvalume Steel
Wall thickness: ¼” on diameters 3” through 8”, 1” air space on diameters 10” through 30”
Ratings / Installation Requirements: Maximum 470°F continuous flue gas temperature. Negative vent pressures only. Install at ¼” per foot slope back towards appliance
Insulation: Insulating air space 3” through 8”
Connection Details: Align the seams and twist left to lock 10” through 30”
Connection Details: Insert the male coupler into the female coupler and use sheet metal screws through holes in the female coupler

DWGD-ZC

DWGD-ZC

Zero clearance grease duct
Description: Zero Clearance and fire rated Grease Duct double wall system
Wall thickness: Inner Liner per UL-1978/-2221 Listing . Outer Jacket 0.025″ (diameters 6 – 24 inch). Outer Jacket 0.035″ (diameters 26 – 36 inch)
Inner diameter: 5-36 inch
Insulation: 3.25″ thick compressed ceramic fiber
Connection: Vee band connection
Locking band: Attached to each part

DWDG +1

DWDG +1

Double wall reduced clearance grease duct
Description: Double Wall reduced clearance grease duct
Wall thickness: Inner Liner per UL-1978 Listing . Outer Jacket 0.025″ (diameters 5 – 24 inch). Outer Jacket 0.035″ (diameters 26 – 36 inch)
Inner diameter: 5-36 inch
Insulation: Ceramic Fiber, 1.5″ thick compressed to 1.25″ space
Connection: Conical
Locking band: Attached to each part

Freestanding Style Industrial Chimneys

Jeremias freestanding chimney systems are manufactured in our German factory. Outside Germany all systems are custom fabricated only.

FSA

FSA

Free-standing, double-wall chimney with a supporting outer wall and a non-expanding inner pipe for exhaust gasses. The FSA system offers flexibility and large heights.
Applications:
– Engines/combined heat and power plants
– Gas/oil boilers
– Biomass
– Chemical exhaust air
– Gas turbine
– Steel production

FSA-X

FSA-X

The FSA-X has multiple inner pipes. The “X” stands for the number of inner pipes. This facilitates the connection of two or more heat producers to the same outer chimney providing a more economical solution.
Applications:
– Engines/combined heat and power plants
– Gas/oil boilers
– Chemical exhaust air
– Gas turbine
– Steel production

FSB

FSB

The FSB is a freestanding, insulated and cladded steel chimney with an inner static supporting flue gas line. This system is usually affixed with one or more brackets to a building.
Application:
– Normal fireplaces
– Oil/gas boiler
– CHP
– Emergency generators
– Special fireplaces
– Suitable until 4500C, but not for solid fuels

FS-RM

FS-RM

The FS-RM is a flexible chimney solution combining a steel (chimney) support mast and stainless-steel chimney elements offering the possibility to customize the chimney at any time to meet new requirements. FS-RM makes it possible to achieve heights up to 30 meters with stainless steel element chimneys.

Industrial Chimneys

Ventilation Towers

Vents

Jeremias ventilation towers combine high functionality and elegant design resulting in a high-quality, efficient functioning tower that compliments the design of any building.

Each FSC system is custom-designed, paying special attention to the needs of each individual client and guaranteeing that the tower will be an eyecatcher, blending in beautifully and fully complimenting the design of your facility while delivering excellent results.

No matter the application, whether an air supply tower with a lamella hood in different shapes or an exhaust air tower, Jeremias technical professionals take into consideration flow resistance and noises.

Exhaust Gas Silencers

Vents

Jeremias offers a wide range of robust flue gas silencers for the industrial sector.

Jeremias manufactures absorption silencers and combined flue gas silencers (consisting of absorption and resonance chambers as-well-as noise insulating cores) with nominal diameters of 400 mm.

The flue gas silencer type is selected according to the source of the noise (for example, generated by oil and gas boilers, fans, wood burning systems, ventilation systems or gas turbines) and attenuation requirements.

Our flue gas silencers are suitable for wet and dry operation and incorporate high-quality materials that provide effective, long-term noise reduction.

Flue Gas Ducts

Vents

Flue gas ducts are made for a robust and safe connection solution between the boiler/engine outlet and the chimney entrance. They can be used as a plug-in system, completely welded, or as a flange system depending on service life. Planning for compensators, flue gas dampers and structural steel supports is done by our experiences project leader, providing professionalism, technical expertise and guaranteed satisfaction.
Specifications:
Temperature: up to 2,0000F
Pressures: up to 30” W.C.
Diameter: up to 8 feet
Thickness: up to 3/16”